LINE REGULATOR FOR USE IN PURE GAS SUPPLY SYSTEMS

This single-stage line pressure regulator is used in gas supply systems for pure, inert, flammable, oxidising gases and gas mixtures up to gas purity 6.0. It is not usable for corrosive and/or toxic gases and their mixtures.

SPECIAL FEATURES:

  • Low outlet pressure
  • Very fine adjustment
  • The large housing diameter of this pressure reducer allows large metal diaphragms and thus very fine adjustment of the back pressure at comparatively high flows down to 250 mbar
  • The line pressure regulator reduces the line pressure with very small hysteresis to very low supply pressures

TECHNICAL DATA

Working temperature: -20°C to +60°C
Inlet/outlet ports: NPT 1/4"f, optional compression fitting
Leakage rate seat: <5x10-6 mbar l/s (Helium)
Leakage rate outside: <1x10-9 mbar l/s (Helium)
Filter: 1x for inlet
1x for each outlet
Weight: 2,7 kg
Flow nominal: 5 m3/h (N2)
Material gas wetted parts:  
   Regulator body: Brass chrome plated
   Regulator diaphragm: Hastelloy
   Regulator seat:
   LPBPVSJ-Version
   LPBPESJ-Version

FKM
EPDM
   Regulator seat:
   LPBPVSJ-Version
   LPBPESJ-Version

FKM
EPDM
   Regulator poppet: Brass
   Regulator seal: PCTFE
Pressure rates line regulator:  
   Inlet pressure: 12 | 40 bar
   Outlet pressure:
   12 bar Version:
   40 bar Version:

250 mbar | 450 mbar | 1300 mbar
250 mbar | 450 mbar | 1300 mbar | 3000 mbar
Pressure gauges rates (pressure rates): 0-300 mbar (250 mbar) | 0-600 mbar (450 mbar) | 0-1600 mbar (1300 mbar) | 0-4000 mbar (3000 mbar)
Contact gauges available – please contact us  
Cracking pressure relief valves: 2 bar (1300 mbar) | 4,6 bar (3000 mbar)
Test in production: Pressure test with Helium of each item
Seat leakage test with Helium of each item
Helium leak test of each regulator against the atmosphere
Test of the functionality of each item
Approvals during development: Type test in accordance with ISO 7291
Additional life cycle test
Electrostatic chargeability test
  • Fulfil requirements according to ISO 80079-36; IEC TS 60079-32-1 and German TRGS 727
  • Usable in EX-areas zones 1 and 2 for gases with explosion risk group I; IIA; IIB; IIC

 

 

Technical Drawings Top

Download Technical Drawings

Acrobat Logo LPBPVSF_drawings.pdf Acrobat Logo LSBPVSF_drawings.pdf